首页> 外文会议>IEEE Annual Report of the Conference on Electrical Insulation and Dielectric Phenomena >Gas-in-oil criteria for the monitoring of self-contained oil-filled power cables
【24h】

Gas-in-oil criteria for the monitoring of self-contained oil-filled power cables

机译:用于监测自包含充油电力电缆的气体 - 油标准

获取原文
获取外文期刊封面目录资料

摘要

Dissolved gas analysis (DGA) initially developed for the monitoring of transformers was recently introduced for in-service diagnostics of power cables. Criteria successfully developed for transformers are not readily applicable to cables because of significant differences in the design and operating characteristics of both systems. The paper presents the development of DGA diagnostic criteria for the maintenance of Hydro-Quebec's power cable network. The diagnostic of a given cable circuit is based on the voltage rating, the individual gas concentration levels, the key gas ratios, the gas formation trends, the years in service, and the load. A new graphical representation of the IEC 599 method for the interpretation of gas ratios was developed in view of its application to power cable diagnostics. This new method, also applicable to transformers, solves most of the undetermined diagnostics given by the IEC method. The whole DGA diagnostic procedure logic is coded in an expert system shell automating the final diagnostic on the condition of the cable insulation.
机译:最初为监测变压器监测的溶解气体分析(DGA)最近被引入了电力电缆的在职诊断。由于两个系统的设计和操作特性有显着差异,因此不容易适用于变压器成功开发的标准。本文介绍了DGA诊断标准的维护水电 - 魁北克电力电缆网络。给定电缆电路的诊断基于电压额定值,单个气体浓度水平,关键气体比,燃气形成趋势,服务中的岁月和负载。考虑到其在电力电缆诊断的应用,开发了用于解释气体比例的IEC 599方法的新图形表示。这种新方法,也适用于变压器,解决了IEC方法给出的大部分未确定的诊断。整个DGA诊断程序逻辑被编码在专家系统外壳中,自动化电缆绝缘条件的最终诊断。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号