首页> 外文会议> >Gas-in-oil criteria for the monitoring of self-contained oil-filled power cables
【24h】

Gas-in-oil criteria for the monitoring of self-contained oil-filled power cables

机译:监控自足式充油电力电缆的油中气体标准

获取原文

摘要

Dissolved gas analysis (DGA) initially developed for the monitoring of transformers was recently introduced for in-service diagnostics of power cables. Criteria successfully developed for transformers are not readily applicable to cables because of significant differences in the design and operating characteristics of both systems. The paper presents the development of DGA diagnostic criteria for the maintenance of Hydro-Quebec's power cable network. The diagnostic of a given cable circuit is based on the voltage rating, the individual gas concentration levels, the key gas ratios, the gas formation trends, the years in service, and the load. A new graphical representation of the IEC 599 method for the interpretation of gas ratios was developed in view of its application to power cable diagnostics. This new method, also applicable to transformers, solves most of the undetermined diagnostics given by the IEC method. The whole DGA diagnostic procedure logic is coded in an expert system shell automating the final diagnostic on the condition of the cable insulation.
机译:最初为监视变压器而开发的溶解气体分析(DGA)最近被引入用于在役电缆的诊断。由于两个系统的设计和操作特性存在很大差异,因此为变压器成功开发的标准不适用于电缆。本文介绍了用于维护魁北克水电局电力电缆网络的DGA诊断标准的发展。给定电缆电路的诊断基于额定电压,单个气体浓度水平,关键气体比率,气体形成趋势,使用年限和负载。鉴于IEC 599方法在电力电缆诊断中的应用,开发了一种新的图形表示法来解释气体比率。这种新方法也适用于变压器,解决了IEC方法给出的大多数不确定的诊断问题。整个DGA诊断程序逻辑均在专家系统的外​​壳中编码,可根据电缆绝缘情况自动进行最终诊断。