首页> 外文会议>Conference on Frontier Academic Forum of Electrical Engineering >Numerical Simulation Calculation Analysis of Very Fast Transient Overvoltage Arcing Characteristics in GIS Under Dynamic Arc Model
【24h】

Numerical Simulation Calculation Analysis of Very Fast Transient Overvoltage Arcing Characteristics in GIS Under Dynamic Arc Model

机译:动态弧模型GIS中非常快速的瞬态过压弧形特性的数值模拟计算分析

获取原文

摘要

In gas insulated substation (GIS), very fast transient over-voltage (VFTO) is caused during the switching operation because of repeated arc reignition. At present only the first arc is considered for numerical simulation of VFTO, which can't describe the character of VFTO exactly, because the time of arc reignition and extinction is difficult to determine. Base on arc dynamic energy equation, the paper confirms the decision condition of arc reignition and extinction, and gets VFTO wave and peak voltage of each node during arc reignition by simulating. Comparing to the two results, it could see that, for the same node, there was not great change in wave forms; the VFTO maximums both on mains side of switching, also this node's peak voltage had the largest difference, base on the first arc peak voltage, approximately 10.78%, which should been attention to for insulation of apparatus.
机译:在气体绝缘变电站(GIS)中,由于重复的弧形重新标准,在开关操作期间引起了非常快速的瞬态过电压(VFTO)。 目前仅考虑第一个弧度用于vfto的数值模拟,这无法描述vfto的特征,因为难以确定的弧度的时间和灭绝的时间。 基于电弧动态能量方程,本文通过模拟,确认电弧协调和灭绝的决策条件,并获得每个节点的VFTO波和峰值电压。 比较两种结果,它可以看到,对于同一节点,波形没有大变化; vfto最大值均在开关的主电源侧,也具有最大的差异,底座在第一电弧峰值电压下,约为10.78%,这应该注意装置的绝缘。