Performance assessment of Synchronous Condensers vs Voltage Source Converters providing grid-forming functions

机译:同步冷凝器的性能评估VS电压源转换器提供网格形成功能

获取原文

摘要

Having sufficient grid-forming sources is one of the necessary conditions to guarantee the stability in a power system hosting a very large share of inverter-based generation. The grid-forming function has been historically fulfilled by synchronous machines. However, with the appropriate control, it can also be provided by voltage source converters (VSC). This work presents a comparison between two technologies with grid-forming capability: the VSC with a grid-forming control coupled with an adequate energy storage system, and the synchronous condensers (SC). Both devices are compared regarding their inertial response, as well as their contribution to the system strength and short-circuit current for an equivalent capacity expressed in terms of apparent power and inertial reserve. Their behaviour following grid disturbances is assessed through time-domain simulations based on detailed electromagnetic transient (EMT) models. The results show that both devices achieve similar performance in the timescale of seconds. For shorter time-windows, however, they present a different behavior: the SC ensures a better stiffness in the first tens of ms following the disturbance, while the VSC offers a faster resynchronization.
机译:拥有足够的网格形成来源是保证托管基于逆变器的电力系统中的稳定性的必要条件之一。网格形成功能已被同步机历史满足。然而,利用适当的控制,它也可以由电压源转换器(VSC)提供。这项工作提出了两种技术之间的比较,具有网格形成能力:VSC具有与适当的能量存储系统的相连和同步冷凝器(SC)耦合。在其惯性响应方面比较两种装置,以及它们对系统强度和短路电流的贡献,以实现表现出明显的功率和惯性储备。通过基于详细的电磁瞬态(EMT)模型来评估跟随电网干扰后的行为。结果表明,两种设备在秒的时间内达到了类似的性能。然而,对于较短的时间窗口,它们呈现了不同的行为:SC确保在干扰后的第一毫秒内更好的刚度,而VSC则提供更快的重新同步。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号