首页> 外文会议>IEEE Madrid PowerTech Conference >Load Encroachment in the Presence of Single-Phase Autoreclosure and Bulk Power Transmission
【24h】

Load Encroachment in the Presence of Single-Phase Autoreclosure and Bulk Power Transmission

机译:在存在单相自动卷云和散装电力传输的情况下负载侵占

获取原文

摘要

The paper discusses how the asymmetrical situation during single-phase autoreclosure influences the protection security and line loadability. First, we analyze the phase current displacement and earth current in single-phase and three-phase tripped conditions and their dependence on system impedance parameters. We then show the effects on the conventional distance protection algorithm and give worst case estimates for the reduction of measured impedance in asymmetrical cases. Simulations using PSCAD and a Digital Twin of Siemens distance relays are presented to give a good assessment of relay behavior and protection security. Lastly, we discuss possible solutions like reduced zone-reach of phase-to-earth loops and use of reactance method.
机译:本文讨论了单相自动曝光过程中的不对称情况如何影响保护安全性和线路加载性。 首先,我们分析单相和三相绊倒条件中的相电流位移和地球电流及其对系统阻抗参数的依赖性。 然后,我们对传统距离保护算法显示了对传统距离保护算法的影响,并给出了在不对称情况下减少测量阻抗的最坏情况估计。 使用PSCAD的模拟和西门子距离继电器的数字双胞胎,以良好的继电器行为和保护安全性评估。 最后,我们讨论可能的解决方案,如降低的地球循环区域和电抗法的使用。