首页> 外文OA文献 >Single-phase AutoReClosure ARC failure on 400 kV combinedcable/overhead line with permanently connected shunt reactor
【2h】

Single-phase AutoReClosure ARC failure on 400 kV combinedcable/overhead line with permanently connected shunt reactor

机译:400 kV组合电缆/架空线与永久连接并联电抗器的单相autoReClosure aRC故障

摘要

This paper demonstrates the results from a detailed study of the dynamic behavior of a shunt reactor compensated 400 kV combined cable/overhead line. This is accomplished by means of theoretical considerations, simulations and measurements. The work presented here is based on a real-life operating 400 kV power system and initiated by Danish TSO Energinet.dk after having measured the voltage of the cable/overhead line after disconnection. A particular decaying dynamic phase voltage containing voltages higher than the voltage before disconnection appeared. A simulation model for the entire system consisting of overhead lines, crossbonded cable sections and shunt reactor has been created in PSCAD/EMTDC and verified against measurements with good results. Main focus has been put on the likelihood of having a successful single-phase autoreclosure ARC in such a combined cable/OHL line.
机译:本文演示了对并联电抗器补偿的400 kV电缆/架空组合线的动态行为进行详细研究的结果。这是通过理论考虑,模拟和测量来实现的。此处介绍的工作基于一个实际运行的400 kV电力系统,由丹麦TSO Energinet.dk在测量断开后的电缆/架空线的电压后启动。出现了一个特定的衰减动态相电压,该电压包含的电压高于断开之前的电压。在PSCAD / EMTDC中创建了由架空线,交叉粘结的电缆段和并联电抗器组成的整个系统的仿真模型,并针对测量结果进行了验证,结果良好。主要关注点是在这样的电缆/ OHL组合线路中成功实现单相自动重合闸ARC的可能性。

著录项

  • 作者

    Bak Claus Leth; Søgaard Kim;

  • 作者单位
  • 年度 2008
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号