Distribution System State Estimation provides an accurate model to assess the real-time condition of the three-phase unbalanced distribution networks. However, the entire estimation is prone to the voltage unbalance at the reference bus (RB), typically assumed with balanced voltage phase angles at the substation. This work enhances the voltage unbalance estimation for traditional three-phase state estimators and demonstrates that many practical situations enable proper estimation of the RB voltage unbalance without the need for special substation models or Phasor Measurement Units (PMUs). A three-phase numerical observability analysis, based on the H matrix, assesses the feasibility of estimating the voltage phase angles at the RB through the coupling elements among different phases. Simulation results on the IEEE test feeders demonstrate the feasibility and the effects of a proper voltage unbalance estimation, showing an overall increased accuracy for the entire network.
机译:分配系统状态估计提供了一种准确的模型,以评估三相不平衡分配网络的实时条件。然而,整个估计容易出于参考总线(RB)处的电压不平衡,通常以变电站的平衡电压相位角度假设。这项工作提高了传统三相状态估计的电压不平衡估计,并表明许多实际情况能够正确估计RB电压不平衡,而无需特殊的变电模型或相量测量单元(PMU)。基于H的三相数值观察性分析Δ 矩阵,评估通过不同阶段之间的耦合元件估计RB处的电压相角的可行性。 IEEE测试馈线的仿真结果表明了适当的电压不平衡估计的可行性和效果,显示了整个网络的总体精度。