首页> 外文会议>International Electrical and Energy Conference >Research on Moisture Assessment of Oil-Paper Insulated Bushing Based on Polarization and Depolarization Current
【24h】

Research on Moisture Assessment of Oil-Paper Insulated Bushing Based on Polarization and Depolarization Current

机译:基于极化和去极化电流的油纸绝缘衬套水分评价研究

获取原文

摘要

High-voltage bushing is an important part of the operation of transformer equipment. In order to accurately and effectively evaluate the moisture condition of the bushing, this paper uses the polarization and depolarization current (PDC) non-destructive measurement method to do it. In the current research, the characteristics of loss peaks and curve fluctuations of tanδ-f curve can judge whether the bushing is evenly damp, but it lacks the judgment of the high moisture position of the internal damp. This paper uses oil-paper samples of different moisture content to make a preliminary qualitative exploration of PDC measurement methods. Then the polarity reversal method is used to judge the bushings with different moisture conditions, Combined with the migration characteristics of hydrolyzed ions in the oil-paper insulation, it is analyzed to verify the effectiveness of the method.
机译:高压衬套是变压器设备操作的重要组成部分。 为了准确且有效地评估套管的水分状况,本文采用偏振和去极化电流(PDC)非破坏性测量方法来进行。 在目前的研究中,Tanδ-F曲线的损耗峰值和曲线波动的特性可以判断衬套是否均匀潮湿,但它缺乏内部潮湿的高湿度位置的判断。 本文采用不同水分含量的油纸样品,对PDC测量方法进行初步定性探索。 然后,极性反转方法用于判断具有不同水分条件的衬套,与油纸绝缘中水解离子的迁移特性相结合,分析了该方法的有效性。