首页> 外文会议>International Electrical and Energy Conference >Experimental analysis of radiated magnetic field based on time frequency method for primary/secondary fusion distribution switch
【24h】

Experimental analysis of radiated magnetic field based on time frequency method for primary/secondary fusion distribution switch

机译:基于初级/二次融合分布开关的时频法的辐射磁场实验分析

获取原文

摘要

Due to various electromagnetic interference, the primary/secondary fusion power distribution switch often has various faults, but the type of interference and evaluation methods considered in the current study are relatively single, which cannot completely simulate the interference intensity and action time in actual operation. This paper firstly describes the electromagnetic interference principle of the primary/secondary fusion distribution switch, selects to build a simulated transient harassment generation device, considers a model 10kV outdoor primary/secondary fusion distribution switch with the stable interference signal, and focuses on the collection of the spatial magnetic field signal near the switch. The magnetic field distribution around the secondary circuit. The results show that under the proposed interference, the instantaneous magnetic field strength on the side of the distribution switch transformer can reach 11000A/m and the characteristic frequency distribution of the interference signal is around 1.3MHz, 12MHz and 20MHz.
机译:由于各种电磁干扰,初级/二次融合配电开关通常具有各种故障,但目前研究中考虑的干扰和评估方法的类型相对单一,其不能完全模拟实际操作中的干扰强度和动作时间。本文首先介绍了初级/二次融合分布开关的电磁干扰原理,选择构建模拟的瞬态骚扰生成装置,将10kV户外初级/次级融合分布开关与稳定的干扰信号进行,并专注于集合开关附近的空间磁场信号。辅助电路周围的磁场分布。结果表明,在所提出的干扰下,分配开关变压器侧的瞬时磁场强度可以达到11000A / m,干扰信号的特征频率分布约为1.3MHz,12MHz和20MHz。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号