首页> 外文会议>International Conference on Electrical Power and Energy Systems >Fuzzy logic based fault detector and classifier for three phase transmission lines with STATCOM
【24h】

Fuzzy logic based fault detector and classifier for three phase transmission lines with STATCOM

机译:基于模糊的基于逻辑的故障检测器和分类三相传输线路

获取原文

摘要

This paper presents the fault detection and classification for shunt faults on transmission lines with Static Synchronous Compensator (STATCOM) using fuzzy logic. The fuzzy logic is implemented by using the fuzzy logic toolbox in MATLAB. The 500kV, 60Hz system is simulated using simulink and simpower systems toolbox in MATLAB. The proposed method uses only the three phase currents for fault detection and classification of faulted phase. The system is simulated for various shunt faults with different fault resistances and with different fault locations between 10 percent and 90 percent of the transmission line. The results from the simulation show that fuzzy logic based fault detector and classifier accurately detects and classifies the faults on transmission system. The proposed method is able to detect and classify the faults for varying fault resistances and fault distances from the relaying point.
机译:本文介绍了使用模糊逻辑的静态同步补偿器(Statcom)对传输线路分流故障的故障检测和分类。模糊逻辑是通过使用MATLAB中的模糊逻辑工具箱来实现的。使用Matlab中的Simulink和Simpower Systems Toolbox进行模拟500kV,60Hz系统。该方法仅使用三相电流进行故障检测和故障阶段的分类。该系统是针对各种具有不同故障电阻的分流器故障模拟,具有不同的故障位置,在输电线的10%和90%之间。仿真结果表明,基于模糊的逻辑的故障检测器和分类器精确地检测并对传输系统的故障进行分类。所提出的方法能够检测和分类与中继点不同的故障电阻和故障距离的故障。