首页> 外文会议>IEEE Conference on Electrical Insulation and Dielectric Phenomenon >Frequency Response of Transformer Winding: A Case Study based on a Laboratory Model
【24h】

Frequency Response of Transformer Winding: A Case Study based on a Laboratory Model

机译:变压器绕组的频率响应:基于实验室模型的案例研究

获取原文

摘要

Many researchers have been studying frequency response analysis measurements and its relevant interpretations. Nowadays, the measurements have been well standardized. However, more objective results interpretation is still needed. This research used a laboratory winding model to enable the simulation of mechanical defects and obtained controlled measurements of its frequency response. The vectfit and the Chinese standard methods were used to compare different interpretations. Results indicated an agreement between the vectfit method and the experimental data, demonstrating that the model has potential of providing a powerful tool to interpretation of power transformer frequency behaviour. Nonetheless, the Chinese standard failed to show the severity of the defects, indicating a normal winding for some cases evaluated. For an overall maintenance strategy, frequency response tests can help taking restorative measures before deterioration reaches a point where failure of the transformer is inevitable.
机译:许多研究人员一直在研究频率响应分析测量及其相关解释。如今,测量已经很好地标准化。但是,仍然需要更多客观的结果解释。该研究使用了实验室绕组模型来实现机械缺陷的模拟并获得其频率响应的受控测量。 VectFit和中国标准方法用于比较不同的解释。结果表明VectFit方法与实验数据之间的一致性,表明该模型具有提供强大的工具来解释电力变压器频率行为。尽管如此,中国标准未能显示缺陷的严重程度,表明某些情况评估的正常绕组。对于整体维护策略,频率响应测试可以在恶化达到变压器不可避免的点之前采取恢复措施。