首页> 外文会议>International Conference on Mechatronics Engineering and Modern Technologies in Industrial Engineering >PR Control of A Three-phase Grid-connected Inverter Under Unbalanced Grid Voltages Condition
【24h】

PR Control of A Three-phase Grid-connected Inverter Under Unbalanced Grid Voltages Condition

机译:PR在不平衡网格电压下控制三相网格连接的逆变器

获取原文

摘要

The effective control of a grid-connected inverter (GCI) under unbalanced grid voltages condition is able to enhance the grid-connected operation ability of the inverter. This paper studies the control scheme of a three-phase GCI with proportional plus resonant (PR) regulators in the stationary αβ frame to remove the power ripples caused by the unbalanced condition and the currents of positive and negative components can be controlled directly without any decomposition. A precise and fast phase-locked loop is also introduced in this paper. Three control targets are achieved on a 2KVA experimental platform of a GCI and the experimental results agree well with the theoretical analysis.
机译:在不平衡电网电压下,在不平衡电网电压下的有效控制电网连接逆变器(GCI)能够提高逆变器的电网连接操作能力。本文研究了三相GCI的控制方案,以静止的αβ帧中的比例加上谐振(PR)调节器,以去除由不平衡状态引起的功率涟漪,并且可以直接控制正面和负部件的电流而没有任何分解。本文还介绍了精确和快速的锁相环。在GCI的2KVA实验平台上实现了三个控制目标,实验结果与理论分析很好。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号