首页> 外文会议>International Conference on Green Transport, Renewable Energy and Environment >Heat Imbalance Analysis of a Hybrid Ground-Source Heat Pump System
【24h】

Heat Imbalance Analysis of a Hybrid Ground-Source Heat Pump System

机译:混合地源热泵系统的热不平衡分析

获取原文

摘要

Operating data in the last two years of a hybrid ground-source heat pump system (HGSHPS) were analyzed, and were contrasted to TRNSYS simulation results. Heat extraction from the borehole heat exchanger (BHE) of ground-source heat pump system (GSHPS) was too much larger than the heat injection, but heat extraction from the borehole thermal energy storage (BTES) of solar assisted GSHPS (SAGSHPS) was too less than the heat storage, in 2012. Serious problem of heat imbalance of BHE occurred, and the GSHPS almost could not work in the late heating season of 2012. An adjusted operating strategy was utilized in 2013. The ground temperature imbalance for GSHPS and heat excess for SAGSHPS were resolved. It is important to monitor the operation of HGSHPS to resolve the heat imbalance problem.
机译:分析了混合地源热泵系统(HGSHPS)的最后两年中的操作数据,与Trnsys仿真结果形成鲜明对比。从地源热泵系统(GSHPS)的钻孔热交换器(BHE)的热萃取量太大而不是热注射,但也是来自太阳能辅助GSHPS(SAGSHPS)的钻孔热能存储(BTES)的热提取少于蓄热,在2012年。发生的BHE的热失衡问题,GSHPS几乎无法在2012年后加热季节工作。2013年使用调整后的操作策略。GSHPS和热量的地面温度不平衡解决了SAGSHPS的过剩。监控HGSHPS的操作是重要的,以解决热不平衡问题。