首页> 外文会议>IEEE PES TD Conference and Exposition >Highly accurate, automatic fault location based on traveling wave principles
【24h】

Highly accurate, automatic fault location based on traveling wave principles

机译:基于旅行波原则的高精度,自动故障定位

获取原文

摘要

Double ended traveling wave fault location has been used on transmission lines for the last decade for accurate and consistent location of permanent and intermittent line faults typically to the nearest tower or span. Choosing whether to monitor the current or voltage component of the wave is discussed and practical examples of sensors given that fit to protection CTs, capacitor PTs and transformer bushings. A variety of sensors means it is now possible to deploy the traveling wave technique on sub transmission networks as well as transmission, a significant advantage to Utilities.
机译:Double Ended Travel Wave Pave故障定位已在过去十年中用于传输线,以便准确,永久性线路故障的准确和一致位置,通常为最近的塔或跨度。选择是否监视波的电流或电压分量,并讨论了用于保护CTS,电容器PTS和变压器衬套的传感器的实际示例。各种传感器意味着现在可以在子传输网络上部署行波技术以及传输,对公用事业的显着优势。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有