首页> 外文会议>Regional Conference on Mechanical and Marine Engineering >A Study of a Heat Exchanger Sizing of a Gas Turbine Inlet Air Cooling for Power Enhancement
【24h】

A Study of a Heat Exchanger Sizing of a Gas Turbine Inlet Air Cooling for Power Enhancement

机译:电力增强燃气轮机入口空气冷却热交换器尺寸的研究

获取原文

摘要

A gas turbine operated at the University Technology PETRONAS Gas Turbine District Cooling Plant produces an average of 3258 kWh with 30% of estimated gas turbine efficiency. A previous study done by the writer has shown of 20% increase in the efficiency of a gas turbine with the implementation of the turbine inlet air cooling. The sizing of the Heat Exchanger needed to be determined as the existing air inlet is only a 30 ft~2 flange attached directly to the compressor of the gas turbine. This studies conclude that a 320 ft~2 heat exchanger is needed in order to reduce the air inlet fluctuations (a range of 23-34°C) to 15°C. By placing the heat exchanger in the gas turbine, a significant Pa pressure loss of approximately 187.55 was experienced.
机译:在大学技术的燃气轮机运行,天体燃气轮机区冷却设备平均为3258千瓦时,估计燃气轮机效率的30%。通过作者完成的先前研究表明,燃气轮机效率随着涡轮机入口空气冷却的实施而言,燃气轮机效率提高了20%。需要确定的热交换器的尺寸,因为现有的空气入口仅是直接连接到燃气轮机的压缩机的30ft〜2凸缘。本研究得出结论,需要320英尺〜2热交换器,以减少空气入口波动(23-34°C的范围)至15℃。通过将热交换器放入燃气轮机中,经历了大约187.55的显着PA压力损失。