摘要

Disconnector switch operation in GIS will generate VFTO, which will harm the equipment. Because there are many limitations in field measurement, simulation can overcome the limitations of experimental research, which can replace test measurement to a certain extent. In this paper, three VFTO suppression methods are simulated in ATP-EMTP. By comparing the VFTO amplitudes of the main equipment before and after the suppression measures, the results show that the paralleling closing resistor can significantly reduce the VFTO amplitude of major equipment. Simplifying wiring also have better suppression but will increase the VFTO amplitude of some devices.Although installing the wave blocker can reduce the VFTO steepness and amplitude on the transformer, but it will produce a serious VFTO on the wave blocker. So the latter two methods can only be applied when appropriate. Through this research, to find the application of the suppression measures, thus effectively reducing the hazard of the VFTO in GIS.
机译:在GIS中的隔离开关操作将产生VFTO,这将损害设备。由于现场测量存在许多局限性,仿真可以克服实验研究的局限性,这可以在一定程度上取代测试测量。在本文中,在ATP-EMTP中模拟了三种VFTO抑制方法。通过比较抑制措施前后主设备的VFTO幅度,结果表明,平行关闭电阻可以显着降低主要设备的VFTO幅度。简化布线也具有更好的抑制,但会增加一些设备的VFTO幅度。虽然安装波波阻断器可以减少vfto陡度和变压器上的幅度,但它将在波阻挡器上产生严重的vfto。所以后两种方法只能在适当时应用。通过这项研究,找到抑制措施的应用,从而有效地减少了GIS中VFTO的危害。