【24h】

Simulation of VFTO Suppression Methods for 1100kV GIS Substation

机译:1100kV GIS变电站VFTO抑制方法的仿真

获取原文
获取原文并翻译 | 示例

摘要

Disconnector switch operation in GIS will generate VFTO, which will harm the equipment. Because there are many limitations in field measurement, simulation can overcome the limitations of experimental research, which can replace test measurement to a certain extent. In this paper, three VFTO suppression methods are simulated in ATP-EMTP. By comparing the VFTO amplitudes of the main equipment before and after the suppression measures, the results show that the paralleling closing resistor can significantly reduce the VFTO amplitude of major equipment. Simplifying wiring also have better suppression but will increase the VFTO amplitude of some devices.Although installing the wave blocker can reduce the VFTO steepness and amplitude on the transformer, but it will produce a serious VFTO on the wave blocker. So the latter two methods can only be applied when appropriate. Through this research, to find the application of the suppression measures, thus effectively reducing the hazard of the VFTO in GIS.
机译:GIS中的隔离开关操作会生成VFTO,这会损坏设备。由于现场测量存在许多局限性,因此模拟可以克服实验研究的局限性,在一定程度上可以代替测试测量。本文在ATP-EMTP中模拟了三种VFTO抑制方法。通过比较抑制措施前后主要设备的VFTO幅度,结果表明,并联闭合电阻器可以显着降低主要设备的VFTO幅度。简化布线也具有更好的抑制效果,但会增加某些设备的VFTO振幅。尽管安装了阻波器可以降低变压器上的VFTO陡度和振幅,但会在阻波器上产生严重的VFTO。因此,后两种方法只能在适当的时候应用。通过这项研究,找到了抑制措施的应用,从而有效降低了GIS中VFTO的危害。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号