首页> 外文会议>International Conference "Actual Problem of Electromechanics and Electrotechnology" >Analysis of the error of the developed method of determination the active conductivity reducing the insulation level between one phase of the network and ground, and insulation parameters in a non-symmetric network with isolated neutral with voltage above 1000 V
【24h】

Analysis of the error of the developed method of determination the active conductivity reducing the insulation level between one phase of the network and ground, and insulation parameters in a non-symmetric network with isolated neutral with voltage above 1000 V

机译:分析确定的确定方法的误差,有源电导率降低网络的一个相位与地之间的绝缘水平,并具有孤立中性的非对称网络中的绝缘参数,电压高于1000 V

获取原文

摘要

In the work the study of the developed method was carried out for reliability by analyzing the error in indirect determination of the insulation parameters in an asymmetric network with an isolated neutral voltage above 1000 V. The conducted studies of the random relative mean square errors show that the accuracy of indirect measurements in the developed method can be effectively regulated not only by selecting a capacitive additional conductivity, which are connected between phases of the electrical network and the ground, but also by the selection of measuring instruments according to the accuracy class. When choosing meters with accuracy class of 0.5 with the correct selection of capacitive additional conductivity that are connected between the phases of the electrical network and the ground, the errors in measuring the insulation parameters will not exceed 10%.
机译:在该工作中,通过分析非对称网络中的绝缘参数的间接确定的误差来进行开发方法的研究,其中具有高于1000 V的隔离中性电压。随机相对均方误差的进行研究表明不仅可以通过选择电容附加电导率,可以有效地调节开发方法中的间接测量的精度,该电容附加电导率连接在电气网络和地面之间,而且还通过根据精度等级选择测量仪器。选择具有0.5的精度等级的仪表,正确选择电容额外的电导率连接在电网和地面之间的相位之间,测量绝缘参数的误差将不超过10%。

著录项

相似文献

  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号