摘要

Accurate fault location is of great significance to ensure the stability of power supply. In this paper, a new fault location method by injecting two high voltage pulses with opposite phase and same pulse width into the line is proposed. By analyzing the propagation characteristics of traveling wave signals on normal lines and fault points, it is theoretically explained that the first voltage traveling wave detected at the non-injected phase comes from the traveling wave reflection at the fault point. VMD (variational mode decomposition) and TEO(Teager operator) are used to extract the arrival time of the wavefront, then the fault location is calculated. Simulation in PSCAD verifies the effectiveness of the proposed method. Compared with the existing methods, the location results obtained by the proposed method are more accurate.
机译:准确的故障位置具有重要意义,以确保电源的稳定性。 在本文中,提出了一种新的故障定位方法,通过将两个具有相反相位和相同的脉冲宽度注入到线路中的两个高压脉冲。 通过分析普通线和故障点上的行波信号的传播特性,理论上解释说,在非注入的相位处检测到的第一电压行驶波来自故障点处的行波反射。 VMD(变分模式分解)和TEO(TEAGER操作员)用于提取波前的到达时间,然后计算故障位置。 PSCAD中的仿真验证了所提出的方法的有效性。 与现有方法相比,通过所提出的方法获得的位置结果更准确。