首页> 外文会议>International Joint Conference on Materials Science and Mechanical Engineering >Reactive power characteristics analysis on emergency stop of doubly fed induction generator
【24h】

Reactive power characteristics analysis on emergency stop of doubly fed induction generator

机译:双馈感应发电机紧急停止的无功功率特性分析

获取原文

摘要

This paper analyzes the reactive power characteristics of the doubly-fed induction . generator (DFIG) during the emergency off-grid process caused by the crowbar protection action. Since the action of the crowbar is much faster than the stator switching, the DFIG would be running with a short-term squirrel cage asynchronous operation. The mathematical model of the DFIG under above situation was proposed in this paper, based on which detailed analysis was given on reactive power demands during squirrel-cage asynchronous state of the DFIG. It is achieved that the amount of reactive power absorption was associated with the initial operating conditions such as the terminal voltage and speed before disconnection, which can be prescribed as the s-Q characteristic of DFIG. Finally, analysis on the measured data of the wind farm disconnected event verified the validity of the model.
机译:本文分析了双馈感应的无功功率特性。发电机(DFIG)在撬棍保护动作引起的紧急外网过程中。由于撬棍的动作比定子切换要快得多,因此DFIG将采用短期松鼠笼式运行异步操作。本文提出了如上所述情况下的DFIG的数学模型,基于该纸张在DFIG的异步状态下对无功功率需求进行了详细分析。实现的是,无功功率吸收量与初始操作条件(例如断开之前)的初始操作条件相关联,这可以被规定为DFIG的S-Q特性。最后,对风电场断开事件的测量数据进行分析验证了模型的有效性。