Distribution line is an important part of power system, it is very important to improve the lightning protection performance of distribution lines effectively to ensure the stability and reliability of power supply. The lightning protection of distribution lines are mainly focused on lightning withstand level calculation, lightning tripping rate calculation, lightning protection performance evaluation and comprehensive lightning protection measures. The paper mainly studies the lightning withstand level and comprehensive lightning protection measures of 10kV distribution lines. Firstly, the actual lightning protection status of the 10kV distribution lines in the Yangjiang area is analyzed and the affect of lightning protection measures are verified based on the statistical results of the lightning failure status, the investigation of the topography. Secondly, based on the electromagnetic transient numerical simulation program PSCAD/EMTDC, the accurate simulation analysis model of lightning overvoltage in distribution lines is established. Thirdly, the influence of line arresters and grounding resistance on lightning withstand level are studied. Finally, the different line arresters arrangement schemes are proposed. The results show that the lightning withstand level of the direct striking and back flashover of distribution line are both very low, at several kilo Amps, and the withstand level relates to the insulator and grounding resistance. The lightning withstand level will be increased by 45% when a set of line arresters are installed every 4 base towers. The protection effect of the line arresters decreases with the increase of the grounding resistance.
机译:配电线是电力系统的重要组成部分,有效地提高配电线路的雷电保护性能,以确保电源的稳定性和可靠性。配电线路的防雷主要集中在闪电耐受水平计算,雷击速度计算,防雷绩效评估和综合防雷措施。本文主要研究闪电耐受水平和综合防雷措施10kV配电线。首先,分析了阳江地区10kV配电线路的实际防雷地位,并根据雷电故障状态的统计结果,对地形的调查来验证防雷措施的影响。其次,基于电磁瞬态数值模拟程序PSCAD / EMTDC,建立了分配线路雷电过电压的准确仿真分析模型。第三,研究了线避孕药和接地阻力对闪电耐受水平的影响。最后,提出了不同的线路避雷器布置方案。结果表明,在几千克排水机处,配电线路直接撞击和背部闪光灯的闪电耐受水平非常低,耐受电平与绝缘体和接地电阻有关。当每4个基座塔楼安装一组线避雷器时,闪电耐受水平将增加45%。避雷器的保护效果随着接地抗性的增加而降低。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号