首页> 外文会议>International Conference on Power System Technology >Study on Lightning Withstand Level and Protection Measures of 10kV Distribution Lines
【24h】

Study on Lightning Withstand Level and Protection Measures of 10kV Distribution Lines

机译:10kV配电线路防雷等级及防护措施的研究

获取原文

摘要

Distribution line is an important part of power system, it is very important to improve the lightning protection performance of distribution lines effectively to ensure the stability and reliability of power supply. The lightning protection of distribution lines are mainly focused on lightning withstand level calculation, lightning tripping rate calculation, lightning protection performance evaluation and comprehensive lightning protection measures. The paper mainly studies the lightning withstand level and comprehensive lightning protection measures of 10kV distribution lines. Firstly, the actual lightning protection status of the 10kV distribution lines in the Yangjiang area is analyzed and the affect of lightning protection measures are verified based on the statistical results of the lightning failure status, the investigation of the topography. Secondly, based on the electromagnetic transient numerical simulation program PSCAD/EMTDC, the accurate simulation analysis model of lightning overvoltage in distribution lines is established. Thirdly, the influence of line arresters and grounding resistance on lightning withstand level are studied. Finally, the different line arresters arrangement schemes are proposed. The results show that the lightning withstand level of the direct striking and back flashover of distribution line are both very low, at several kilo Amps, and the withstand level relates to the insulator and grounding resistance. The lightning withstand level will be increased by 45% when a set of line arresters are installed every 4 base towers. The protection effect of the line arresters decreases with the increase of the grounding resistance.
机译:配电线路是电力系统的重要组成部分,有效提高配电线路的防雷性能对于确保供电的稳定性和可靠性至关重要。配电线路的防雷主要集中在防雷等级计算,防雷跳闸率计算,防雷性能评估和综合防雷措施上。本文主要研究10kV配电线路的防雷等级和综合防雷措施。首先,对阳江地区10kV配电线路的实际防雷状况进行了分析,并根据雷击故障状况的统计结果,对地形进行了调查,验证了防雷措施的影响。其次,基于电磁暂态数值仿真程序PSCAD / EMTDC,建立了配电线路雷电过电压的精确仿真分析模型。第三,研究了避雷器和接地电阻对雷电承受水平的影响。最后,提出了不同的线路避雷器布置方案。结果表明,配电线路的直接击穿和反闪击的雷电承受力都非常低,只有几千安培,并且承受力与绝缘子和接地电阻有关。如果每4个基础塔安装一组避雷器,则雷电承受能力将提高45%。避雷器的保护作用随着接地电阻的增加而降低。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号