首页> 外文会议>Conference on Diagnostics in Electrical Engineering >The Experimental Measurements of Surface Leakage Current on the Insulator Model
【24h】

The Experimental Measurements of Surface Leakage Current on the Insulator Model

机译:绝缘子模型表面漏电流的实验测量

获取原文

摘要

The insulator is one of the important elements of the transmission system that electrically separates and mechanically connects two points wit h different potentials. In presented contribution we are focused on the measurement of surface leakage current on the insulator model under various pollution conditions. To simulate environmental pollution, a conductive electrolyte layer with different conductivity was used. Experimental measurements on the physical model point to the fact that the most optimal frequency of the sine wave test voltage is 1 kHz. It has also been shown that surface leakage current is increasing as the degree of pollution increases, under wet conditions. Monitoring the leakage current along the surface of the external insulation may be used as an indicator of contamination of the external insulation.
机译:绝缘体是传输系统的重要元件之一,其电分离和机械地连接两个点不同的电位。在呈现的贡献中,我们的专注于各种污染条件下绝缘模型上的表面漏电流的测量。为了模拟环境污染,使用具有不同导电性的导电电解质层。物理模型的实验测量指向正弦波测试电压最佳频率为1 kHz的事实。还表明,随着污染程度的增加,表面漏电流在潮湿条件下增加。监测沿着外部绝缘表面的漏电流可以用作外部绝缘污染的指示。