Regular defrost of air cooling coils is necessary to restore cooling performance but creates parasitic load onthe refrigeration system and can result in short term temperature fluctuations in the refrigerated space. A newmethod that directly links defrost heat load to latent loads in the refrigerated facility and likely melt waterflows is presented. Practical guidance, that is informed by both this method and measurements for actualsystems, is provided for the optimization of defrost frequency and duration. Key aspects are: to have amethod that terminates defrost once the coil is free of frost and there is no more melt water to avoidunproductive heating; and to vary the frequency of defrost to match the latent load the facility experiences sothere is a similar frost loading at the start of each defrost.
机译:空气冷却线圈的定期除霜是恢复冷却性能,但造成寄生载量制冷系统,可导致冷藏空间中的短期温度波动。一个新的直接将解冻热负荷与冷藏设施中的潜入载荷直接链接到潜入水的方法流动呈现。实际指导,通过这种方法和实际测量来了解情况提供系统,用于优化除霜频率和持续时间。关键方面是:有一个一旦线圈不含霜,就终止除霜的方法,并且没有更多的熔体水来避免不生产加热;并改变除霜的频率,以匹配设施的潜伏负载在每个除霜开始时存在类似的霜加载。