首页> 外文会议>International conference on electrical and information technologies for rail transportation: electrical traction >Influence Analysis of the Grounding Grid of Communication Tower Base on Lightning Signal
【24h】

Influence Analysis of the Grounding Grid of Communication Tower Base on Lightning Signal

机译:通信塔基地接地网对雷电信号的影响分析

获取原文
获取外文期刊封面目录资料

摘要

Communication tower is often close to machine room. When the lighting strikes the communication tower, it raises electrical potential of grounding grid and transient ground potential raise could damage weak electrical equipment in machine room. In order to solve this problem, in this paper, a response calculation model under the condition of the lightning transient was established, which was based on the construction drawing of a communication tower and machine room grounding grid in Bao-Lan PDL (Passenger Dedicated Line). This model analyzed potential changes under the conditions of various factors when the lightning current injected grounding grid, including two grounding grid is equipotent connected or not, different distances and soil resistivity between two grounding grid, etc. Computational results show that transient ground potential of the machine room can reduce by 70% when the distance of two grounding grid increased from 5 to 20 m, and transient ground potential can be 10 times higher when two grounding grid is equipotent connected. Finally, the propose suggestions related to requirements engineering based on these analysis.
机译:通信塔通常靠近机房。当照明撞击通信塔时,它会提高接地网格的电位,瞬态地面潜力升高可能会损坏机房中的电气设备弱电设备。为了解决这个问题,在本文中,建立了雷差瞬态条件下的响应计算模型,基于Bao-LAN PDL的通信塔和机房接地网格的施工图(乘客专用线)。这种模型在各种因素的条件下分析了闪电电流注入接地网格的情况下的潜在变化,包括两个接地网格在等待的连接或不等待,两个接地网格之间的不同距离和土壤电阻率等。计算结果表明瞬态地面潜力当两个接地网格增加到20μm时,机房可以减少70%,当两个接地网格相连时,瞬态地电位可能会越高10倍。最后,提出了基于这些分析的需求工程的建议。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号