首页> 外文会议>International Tropical Renewable Energy Conference >Simulation of Adsorber Tube Diameter's Effect on New Design Silica Gel-Water Adsorption Chiller
【24h】

Simulation of Adsorber Tube Diameter's Effect on New Design Silica Gel-Water Adsorption Chiller

机译:吸附管直径对新设计硅胶水吸附冷却器的影响

获取原文

摘要

A new design of silica gel-water adsorption chiller is proposed. The design configuration is composed of two sorption chambers with compact fin tube heat exchangers as adsorber, condenser, and evaporator. Heat and mass recovery were adopted in order to increase the cooling capacity. Numerical modelling and calculation were used to show the performance of the chiller with different adsorber tube diameter. Under typical condition for hot water inlet/cooling water inlet/chilled water outlet temperatures are 90/30/7oC, respectively, the simulation results showed the best average value of COP, SCP, and cooling power are 0.19, 15.88 W/kg and 279.89 W using 3/8 inch tube.
机译:提出了一种新的硅胶水吸附冷却器。设计配置由具有紧凑型翅片管热交换器的两个吸附腔作为吸附器,冷凝器和蒸发器组成。采用热量和质量恢复以增加冷却能力。数值建模和计算用于显示具有不同吸附管直径的冷却器的性能。在热水入口/冷却水入口/冷却水出口温度的典型条件下分别为90/30 / 7oC,模拟结果显示了COP,SCP和冷却功率的最佳平均值为0.19,15.88W / kg和279.89 w使用3/8英寸管。