首页> 外文会议>International Conference on Machinery, Electronics and Control Simulation >Analysis and Prevention of Tubeburst in Rear Platen Superheater of Boiler
【24h】

Analysis and Prevention of Tubeburst in Rear Platen Superheater of Boiler

机译:锅炉后压板过热器管丸分析与预防

获取原文

摘要

Tube burst occurred on Rear Platen Superheater in No.4 boiler of a power plant. Failed to timely discharge condensate water after an emergency shutdown boiler, and then start again, which leading to water blocking in superheater unit caused tube burst. Contrasting the water blocking accidents recent years in this boiler, corresponding preventive measures are formulated, which have certain reference value to theproblems of tubeburst caused by water blocking of the same type boiler.
机译:管突发发生在电厂4号锅炉的后压板过热器上。紧急关闭锅炉后未能及时排出冷凝水,然后再次启动,导致过热器单元中的水堵塞导致管爆。对比该锅炉近年来的水堵塞事故,配制了相应的预防措施,对该型锅炉的水堵塞引起的管虫病问题具有一定的参考值。