For wind farms consisting of double-fed wind turbines with centralized compensation device SVC, a method was proposed based on a minimum of reactive power compensation, utilization of installed reactive power compensation device SVC and double-fed unit's reactive ability to achieve reactive power optimization. According to actual reactive power generation capability of Double-fed wind turbines and reactive power compensation device SVC, wind Farm automatic voltage control system distributes reactive power with a network Loss minimum of the objective function, this allocation method can play DFIG reactive power regulation capability and can reduce the loss of wind farms. The simulation results show the proposed scheme can effectively reduce the wind farm power losses and improve voltage stability margin.
机译:对于由具有集中补偿装置SVC的双馈风力涡轮机组成的风电场,提出了一种基于最小反应功率补偿的方法,利用安装的无功补偿装置SVC和双馈单元的反应能力实现无功功率优化。根据双馈风力涡轮机的实际无功发电能力和无功补偿装置SVC,风电场自动电压控制系统通过网络损耗分配无功功率的目标函数,这种分配方法可以发挥DFIG无功功率调节能力和可以减少风电场的损失。仿真结果表明,所提出的方案可以有效地降低风电场功率损耗并改善电压稳定性边缘。