首页> 外文会议>European Wind Energy Association Annual Conference and Exhibition >Control of HVDC Diode Rectifier connected off-shore wind farm during cable faults in multi-terminal HVDC grids
【24h】

Control of HVDC Diode Rectifier connected off-shore wind farm during cable faults in multi-terminal HVDC grids

机译:HVDC二极管整流器在多终端HVDC网格中连接岸上风电场的偏离风电场

获取原文

摘要

The presented work shows the proof-of-concept operation of a HVDC diode rectifier (DR) station connected a multi-terminal HVDC grid. Previous work by the authors and others has shown that a wind power plant WPP can adequately control the off-shore ac-grid frequency and current and also deliver optimum power to the HVDC grid mainly in point-to-point configuration. This work aims to show the operation of the HVDC-DR in a multi-terminal HVDC grid and to study up to which extent the WPP control can be used to minimise the currents flowing through the HVDC-DR station during cable (pole-to-ground) faults. It has been found that reasonably fast DR station current reduction can be achieved and hence an active control of the WPP can help on simplifying the protections of the DR station in a muti-terminal environment.
机译:所呈现的工作显示了HVDC二极管整流器(DR)站的概念证明操作连接了多终端HVDC网格。以前的工作由作者和其他人表明,风电厂WPP可以充分控制离岸交流电网频率和电流,并主要为HVDC网格提供最佳功率,主要是点对点配置。这项工作旨在显示多终端HVDC网格中的HVDC-DR的操作,并在何种程度上学习WPP控制在电缆期间最小化流过HVDC-DR站的电流(极点 - 地面)故障。已经发现,可以实现合理的快速博士电流降低,因此可以帮助简化Muti终端环境中DR站的保护的主动控制。