首页> 外文会议>International Symposium on Heating, Ventilation and Air Conditioning >Experimental Study on Heating Performance of Air - source Heat Pump with Water Tank for Thermal Energy Storage
【24h】

Experimental Study on Heating Performance of Air - source Heat Pump with Water Tank for Thermal Energy Storage

机译:水箱热源热泵加热性能的试验研究热能储存

获取原文

摘要

Through the experiment, the coefficient of performance (COP) of air source heat pump with changing water temperature in the tank was studied, when the ambient temperature remains almost unchanged. Then the COPs of the air source heat pump at different supply and return water temperatures were calculated out based on the tested modeLThe results showed that COP equals 3.1, when the supply/return? water temperature was 21癈, and it would decrease by 0.04 with every 1癈 temperature dropping; when the water temperature reached 55癈, COP stood at only 0.74, and the water temperature rose 1 癈, COP reduced 0.12 .For the supply and return water of 50癈 / 40癈 compared to that of 50癈 / 45癈, COP increased by 10.3%; similarly, for 45癈 / 40癈 compared to 50癈 / 40癈, COP increased by 12.9% .The system COP decreased with increasing supply and return water temperatures, and the rate of reduction was affected by the heat loss of the piping system.
机译:通过实验,研究了气源热泵的性能系数(COP),当环境温度仍然保持不变时,研究了罐中的水温变化的水温。然后根据测试模型计算出不同供应和返回水温的空气源热泵的警察,结果表明COP等于3.1,当供应/返回时?水温为21‰,每1次温度滴加将减少0.04;当水温达到55‰时,COP仅为0.74,水温上升1‰,COP减少0.12。对于50癈/ 40癈的供应和返回水为50癈/ 45‰,COP增加10.3%;同样,对于45×/ 40次,COP增加了12.9%。随着供水和返回水温的增加,系统警察减少,减少速率受管道系统的热量损失的影响。