Experimental Study on the Radiant Cooling Load of Floor Based on the Radiant Time Series Method

机译:基于辐射时间序列方法的地板辐射冷却负荷的实验研究

获取原文

摘要

A calculation method about the radiant cooling load of floor which is based on radiant time series (RTS) method is presented: With the use of radiant time factors, radiant cooling load can be easily calculated from the radiant heat gain. Based on experimental data of total heat gain and total cooling loads collected within 24-hours, radiant heat gain of floor can be calculated through convection and radiation separating method, using PRF/RTF Generator software to calculate the radiant time factor of floor;; the radiant cooling load of floor is calculated and compared with the measured values. The results for the 5 experimental conditions show that the radiant cooling load of floor peak error is less than 2.3% comparing with the value which is calculated by radiant time series method, and average error is not more than 3.2%. Its mean absolute error is 1.2% and 1.7% respectively. The experimental study indicated that convection and radiation separating method on wall could calculate the radiant cooling load of floor.
机译:介绍了基于辐射时间序列(RTS)方法的地板辐射冷却负荷的计算方法:利用辐射时间因素,可以从辐射热增益容易地计算辐射冷却负荷。基于24小时内收集的总热量增益和总冷却载荷的实验数据,可以通过对流和辐射分离方法计算地板的辐射热增益,使用PRF / RTF发生器软件计算地板的辐射时间因素;计算地板的辐射冷却负荷,并与测量值进行比较。 5实验条件的结果表明,与通过辐射时间序列方法计算的值比较的辐射冷却负荷小于2.3%,平均误差不超过3.2%。其平均绝对误差分别为1.2%和1.7%。实验研究表明,墙壁上的对流和辐射分离方法可以计算地板的辐射冷却负荷。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号