首页> 外文会议>International Symposium on Heating, Ventilation and Air Conditioning >The Experimental Research on the Heating and Cooling Performance of Light Floor Radiant Panels
【24h】

The Experimental Research on the Heating and Cooling Performance of Light Floor Radiant Panels

机译:轻质辐射板加热和冷却性能的实验研究

获取原文

摘要

The steady state and dynamic performance of light radiant floor panels under heating and cooling conditions are studied in this paper by experiments. The surface temperature, the heating and cooling capacities are measured under different water supply temperature when the temperature of the room is stable. Through the tests, the heating and cooling capacities at different water supply temperature were obtained under steady conditions. For example, when the water supply temperature is 33°C, the heating capacity of the panel is about 76W and the data measured in the test is 75.9. The time constant of the light floor radiant panel is about 30 min and is much smaller than that of traditional concrete floor.
机译:通过实验在本文中研究了在加热和冷却条件下的光辐射地板的稳态和动态性能。当房间的温度稳定时,在不同的供水温度下测量表面温度,加热和冷却能力。通过测试,在稳定的条件下获得不同供水温度的加热和冷却能力。例如,当供水温度为33°C时,面板的加热容量约为76W,测试中测量的数据为75.9。轻质地板辐射板的时间常数约为30分钟,远小于传统混凝土地板。