摘要

How to prevent the hot air entering the outdoor unit is thus critical for Split-type air conditioner (AC) operation temperature control. This investigation studied the influence of louver installation (angle and spacing) and outdoor AC unit arrangement (style and location) on the system ventilation using computational fluid dynamics (CFD) technique. With the louver spacing increasing and the distance between neighbouring outdoor AC units decreasing, the working temperature increases. Considering heat dissipation and protecting machines from rainwater, the optimum louver angle is 100 degrees. The vertical arrangement for outdoor units is more beneficial to exhaust hot air than the horizontal arrangement. In conclusion, in order to reduce operation temperature while saving energy, the following design points are recommended: a. Vertical arrangement for outdoor units; b. Larger distance between neighbouring outdoor units; c. Smaller louver spacing; d. 100 degrees for the louver angle.
机译:如何防止进入室外单元的热空气对于分流式空调(AC)操作温度控制至关重要。本研究研究了百叶窗安装(角度和间距)和户外交流单元布置(风格和位置)对使用计算流体动力学(CFD)技术的系统通风影响。随着百叶窗间距的增加,邻近室外交流单位之间的距离减小,工作温度增加。考虑到雨水的散热和保护机,最佳的百叶窗角度为100度。用于室外单元的垂直布置与排出热空气比水平排列更有益。总之,为了降低运营温度,同时节省能源,建议使用以下设计点:a。户外单位的垂直布置;湾邻近室外单位之间的较大距离; C。较小的百叶窗间距;天。百叶窗角度100度。