摘要

Starting function in distance relay design is a crucial in order to detect a short circuit in power system. However, this function prove vulnerable to distance relay operation as it could falsely send a tripping signal during power swing. To overcome those issues, this paper presents a simple and effective adaptive protection algorithm for power swing false tripping prevention based on Under Impedance Fault Detector (UIFD) characteristics. In order to evaluate the effectiveness of the proposed scheme, the testing has been conducted under IEEE 39 bus system. Simulation results prove that the scheme can be reliably deployed for identifying the power swing conditions and adjusting the relay setting accordingly.
机译:距离继电器设计中的起始功能是一个至关重要的,以便检测电力系统的短路。然而,这种功能证明容易受到距离继电器操作,因为它可以在动力摆动期间错误地发送跳闸信号。为了克服这些问题,本文提出了一种基于阻抗故障检测器(UIFD)特性的功率摆误跳闸预防的简单有效的自适应保护算法。为了评估所提出的方案的有效性,在IEEE 39总线系统下进行了测试。仿真结果证明了该方案可以可靠地部署用于识别动力摆动条件并相应地调节继电器设置。