首页> 外文会议>International Conference on Performance-based Fire and Fire Protection Engineering >Research on smoke exhaust effect at different installation height of mechanical exhaust port in ring corridor of high-rise building
【24h】

Research on smoke exhaust effect at different installation height of mechanical exhaust port in ring corridor of high-rise building

机译:高层建筑环路走廊机械排气口的不同安装高度烟雾废气效应研究

获取原文

摘要

In high-rise building fire, smoke is the main cause of fire spreading and casualties. As a necessary evacuation route, it's very important for both evacuation and firefighting to ensure the effectiveness of smoke exhaust in corridor. While in mechanical exhaust system in corridor, the height of the exhaust port is a main factor that influences the smoke exhaust effect. FDS software was used in this paper to carry on the numerical simulation. Smoke exhaust effect under different working conditions were studied through comprehensive analysis of the smoke layer temperature and visibility in annular corridor with different mechanical smoke exhaust port height. Results show that installation height of the mechanical smoke exhaust port has some influence on smoke layer temperature and visibility. With the lower of the installation height of mechanical smoke exhaust port, smoke layer temperature at 1.5m height of corridor rises gradually, and visibility reduces gradually. All above can provide some reference for designing mechanical exhaust system in ring corridor of high-rise buildings.
机译:在高层建筑火灾中,烟雾是火蔓延和伤亡的主要原因。作为必要的疏散路线,对疏散和消防来说是非常重要的,以确保走廊中的烟雾排气的有效性。在走廊中的机械排气系统中,排气口的高度是影响烟雾废气效果的主要因素。本文使用了FDS软件以进行数值模拟。通过对具有不同机械烟雾排气口高度的烟雾层温度和环形走廊的可见性研究了不同工作条件下的烟雾废气效应。结果表明,机械烟雾排气口的安装高度对烟雾层温度和可见性有所影响。由于机械烟雾排气口的安装高度较低,烟雾层温度在1.5米的走廊高度逐渐上升,并且可视性逐渐减少。以上所有目的都可以为设计高层建筑的环形走廊中的机械排气系统提供一些参考。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号