首页> 外文会议>International Conference on Insulating Materials, Material Application and Electrical Engineering >Effects of Insulation Structure on Electric Field Distribution of Valve-Side Outlet Device of Converter Transformer
【24h】

Effects of Insulation Structure on Electric Field Distribution of Valve-Side Outlet Device of Converter Transformer

机译:绝缘结构对转换器变压器阀侧出口装置电场分布的影响

获取原文

摘要

The valve-side outlet device of the converter transformer is one of the key components of the converter transformer. The insulation structure design is the key technology for the design and manufacture of the outlet device. The insulation structure and electric field distribution of the outlet device have great influence on technical performance and safety. Based on the finite element method and ANSYS simulation software, under the AC and DC electric field distributions of the parts of the straight tube-shaped and allotype-shaped insulation structure were simulated, and the influence of the outlet device's operation characteristics and safety under AC and DC electric field was analyzed. The result shows that: 1 Under the AC voltage, the electric field distribution of the valve side outlet device depends on the relative permittivity of the material; the DC voltage depends on the resistivity of the material; 2 the insulation structure has a great influence on the electric field distribution of the outlet device.
机译:转换器变压器的阀侧出口装置是转换器变压器的关键部件之一。绝缘结构设计是出口装置设计和制造的关键技术。出口装置的绝缘结构和电场分布对技术性能和安全有很大影响。基于有限元方法和ANSYS仿真软件,在模拟了直管形状和单型绝缘结构的部件的AC和DC电场分布下,以及AC下的出口装置的操作特性和安全性的影响分析了直流电场。结果表明:1在交流电压下,阀侧出口装置的电场分布取决于材料的相对介电常数;直流电压取决于材料的电阻率; 2绝缘结构对出口装置的电场分布具有很大的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号