首页> 外文会议>International Conference on Mechatronics and Industrial Informatics >Locating Method of Single-phase Grounding Fault in Small Current Grounding System Based on Distribution Automation
【24h】

Locating Method of Single-phase Grounding Fault in Small Current Grounding System Based on Distribution Automation

机译:基于分布式自动化的小型电流接地系统单相接地故障定位方法

获取原文

摘要

In case of the arc suppression coil for neutral point grounding of small current grounding system, when single-phase grounding fault occurs, due to the arc suppression coil for fault line of the compensation effect of the zero sequence current, the fault features is not obvious, it can't implement the fault line selection and fault point location. This paper puts forward a method of change fault lines zero sequence current shortly, namely a resistance inductance (RL) series branch parallel in arc suppression coil, the series branch acts on the system shortly and changes arc suppression coil compensation degree temporarily in single-phase grounding fault. The change of zero sequence residual current only appears the loop from the neutral point to the fault point via the fault line, using FTU (feeder terminal units) on lines monitor the change of zero sequence current on each nodes for fault regional location. And prove this theory the feasibility of the by using MATLAB software of system modeling simulation method.
机译:如果发生用于小电流接地系统的中性点接地的电弧抑制线圈,当发生单相接机故障时,由于避压效果的断层线的闪频抑制线圈,故障功能不明显,它无法实现故障行选择和故障点位置。本文提出了一种改变故障线零序电流的方法,即弧形抑制线圈平行的电阻电感(RL)系列分支,串行在系统上发挥作用,并在单相中暂时改变电弧抑制线圈补偿程度接地错误。零序列剩余电流的变化仅通过故障线路从中性点到故障点的环路,在线上使用FTU(馈线端子单元)监控每个节点上的零序电流的变化,用于故障区域位置。并证明这一理论通过使用MATLAB软件的系统建模模拟方法的可行性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号