In 2013, CSG installed three ± 200Mvar STATCOMs on the 500kV substations which are adjacent to the receiving ends of multiple HVDC lines. This paper describes a test bed based on the RTDS Simulator that was developed to analyze the impacts of installing these STATCOMs. The impacts of the STATCOMs on voltage recovery and (U) HVDC fault recovery were investigated. The study shows the use of multiple STATCOMs can lead to an improvement in the voltage recovery capability at the inverter station, reduce the occurrence of commutation failures for some faults and improve HVDC power recovery. For some contingencies such as a circuit breaker failure, the improvements were significant. Meanwhile, for other contingencies of long time faults such as commutation failures caused by circuit breaker failure, the STATCOMs had negligible benefit.
机译:2013年,CSG在500kV变电站上安装了三个±200mvar Statcom,与多个HVDC线路的接收端相邻。本文介绍了一种基于RTDS模拟器的试验台,该试验床是开发的,用于分析安装这些Statcoms的影响。 STATCOMS对电压恢复和(U)HVDC故障恢复的影响进行了研究。该研究表明,使用多种Statcom可以导致逆变器站的电压恢复能力的改善,减少一些故障的换向故障的发生,提高HVDC电力恢复。对于一些诸如断路器故障的突发事件,改善是显着的。同时,对于长时间故障的其他突发事件,如断路器故障引起的换向故障,但统计组织的利益可忽略不计。