首页> 外文会议>International Conference on Civil, Architectural and Hydraulic Engineering >Discussion On The Design Of Freezing Dehumidification-Based Radiant Air-Conditioning System
【24h】

Discussion On The Design Of Freezing Dehumidification-Based Radiant Air-Conditioning System

机译:浅谈冻除湿式辐射空调系统的设计

获取原文

摘要

For the purpose of realizing non-dewfall condition of the radiant panels, low energy consumption and nice comfort of the freezing dehumidification-based radiant air-conditioning system, the design temperature and humidity of the room were figured out according to the mean comfort index of human body during the design. And in order to lower the energy consumption, the necessity of the reasonable load allocation between the dehumidification unit and the radiant unit was discussed by means of the calculation with the quasi heat-humidity-ratio line. As a result, much more precise design parameters were acquired through the approximation calculation. And it was proven to be a good design method by applying these parameters to the design of the reading rooms of the library. In the design example of the reading room, the load ratio between the dehumidification unit and the radiant unit was 48 to 52, and the recirculation air flow rate of the dehumidification unit was not less than 36.8% of the total air rate of the room.
机译:用于实现辐射板的非结露状态,能耗低和冷冻基于除湿的辐射空调系统的好的舒适的目的,房间的设计温度和湿度根据的平均舒适度指数计算出在设计期间的人体。并且为了降低能量消耗,通过用准热湿度比线的计算讨论了除湿单元与辐射单元之间合理的负载分配的必要性。结果,通过近似计算获得了更精确的设计参数。通过将这些参数应用于图书馆阅读室的设计,被证明是一个很好的设计方法。在读房间的设计示例中,除湿单元和辐射单元之间的负载比为48至52,除湿单元的再循环空气流速不小于房间总空气速率的36.8%。