首页> 外文会议>International Conference on Energy, Environment and Sustainable Development >Causes Analysis and Treatment Measures for Excess SiO_2 Content in a 300MW Unit Boiler Water
【24h】

Causes Analysis and Treatment Measures for Excess SiO_2 Content in a 300MW Unit Boiler Water

机译:在300MW单位锅炉水中导致过量SiO_2含量的分析和处理措施

获取原文

摘要

According to the characteristics of silicon in water, analysis is implemented for the excess SiO_2 content in a 300MW unit boiler water. Serious excess SiO_2 content in the economizer inlet water and boiler water is caused by high-pressure heater leakage. In addition, SiO_2 content increases with the raising feedwater temperature, because colloidal silicon solubility increases with the raising feedwater temperature. Colloidal silicon in water is induced by condenser tiny leakage. High-pressure heater plugging must be handled. Improving activated charcoal filters washing and boiler blow-off frequency can be used to reduce the impact of colloidal silicon on boiler and ensure safe operation of the boiler.
机译:根据水中硅的特点,在300MW单位锅炉水中实现了过量的SiO_2含量的分析。经济型器进水和锅炉水中的严重过量SiO_2内容是由高压加热器泄漏引起的。另外,SiO_2含量随着升高的供水温度而增加,因为胶体硅溶解度随着提高给水温度而增加。水中的胶体硅通过冷凝器微小泄漏诱导。必须处理高压加热器堵塞。改善活性炭过滤器洗涤和锅炉吹除频可用于减少胶体硅对锅炉的影响,并确保锅炉的安全操作。