首页> 外文会议>IEEE International Energy Conference and Exhibition >Safety evolution of residential microsystems
【24h】

Safety evolution of residential microsystems

机译:住宅微系统的安全进化

获取原文

摘要

Utilities typically supply low-voltage, single-phase residential units using a radial layout, which constitutes a common distribution system for the dwelling units. In typical US and EU distribution systems, a faulted unit may affect the healthy ones within the same distribution system, due to the transfer of ground potentials, sometime dangerous for magnitude or persistence. Ground potentials appear during a fault over the building grounding system (BGS), via the PE, if present, and via the common extraneous-conductive-parts (EXCP). In Europe, TT system is imposed to residential units and the PE is not permitted to be connected to the utility neutral wire at the service entrance of the building. Some of the European utilities, in fact, cannot guarantee the continuity, as well as the absence of potentials, of the neutral conductor, which serves, indeed, many users.
机译:公用事业公司通常使用径向布局提供低压,单相页住宅单元,该径向布局构成了居住单元的公共配送系统。在典型的美国和欧盟分发系统中,由于地面电位的转移,故障单元可能会影响相同分配系统内的健康,因为造成地面电位的某个危险。在建筑物接地系统(BGS)的故障期间,通过PE,如果存在,并且通过常用的外来导电部分(EXCP),地面电位出现接地电位。在欧洲,TT系统施加到住宅单元,并且不允许PE连接到建筑物服务入口处的公用事业线。事实上,一些欧洲公用事业实际上不能保证中立指挥的连续性,以及缺乏潜力,确实是许多用户。