首页> 外文会议>IEEE International Energy Conference and Exhibition >The golden section and the ground resistance
【24h】

The golden section and the ground resistance

机译:金截面和地电阻

获取原文

摘要

In the Fifties' of the last century, Italian and North American Authors explained that the systematic error αA on the measurement of the ground resistance, related to the close distance D of the auxiliary current electrode B, can be offset, during the measurement, leading the voltage probe at a distance, with respect to the test grounding system A, equal to 0.618?D, when A and B can be considered as punctiform electrodes with respect to their distance. This paper gives the explanation of physical meaning of the 0.618 method and demonstrate that we' re dealing with golden section. The paper points out the unclear or incorrect aspects of the traditional treatment.
机译:在上个世纪的五十年代,意大利和北美作者解释说,在测量期间,与辅助电流电极B的近距离D相关的系统误差αa在辅助电流电极B的近距离d的测量。距离的电压探针相对于测试接地系统A,等于0.618≤d,当A和B相对于它们的距离被视为点状电极时。本文给出了0.618方法的物理含义的解释,并证明我们正在处理金块。本文指出了传统治疗的不明确或不正确的方面。