首页> 外文会议>INMR World Congress >Achieving Long Service Life from Transmission Line Arresters
【24h】

Achieving Long Service Life from Transmission Line Arresters

机译:从传输线避雷器实现长期使用寿命

获取原文

摘要

Many transmission line surge arresters (TLSA) have been suspended from phase conductors, adding mass that creates a new mechanical node between insulator suspension clamps and Aeolian vibration dampers. This placement interferes with damper performance, and may shorten the conductor service life. Mitigations include repositioning the dampers, inspecting more frequently or selecting other installation configurations. A case study shows appropriate consideration on these factors for installation of arresters on a new 230-kV line as an alternative to continuous counterpoise.
机译:许多传输线浪涌避雷器(TLSA)已被悬挂在相导体中,添加质量,在绝缘体悬架夹和风振振动器之间产生新的机械节点。这种放置干扰了阻尼器性能,并且可以缩短导体使用寿命。缓解包括重新定位阻尼器,更频繁地检查或选择其他安装配置。案例研究表明,在新的230 kV线上安装避难所的这些因素是适当的考虑因素,作为连续对抗的替代方案。