This article analysis the running conditions and existing problems of air conditioning system for existing public buildings in the cold and serious cold regions in winter, and compares analysis of the solution of the anti freezing measures for the fresh air unit, introduces the recovery exhaust energy by the means of heat exchange to resolve the existing problems of air conditioning system in winter. The results show that the outdoor temperature changes from -25~10°C degree, the degree of air supply can reach more than 10 degree, which means that system which recovers the exhaust energy can preheat the fresh air more than 10 degree. The COP of recovery fresh air heat pump units reaches more than 3.8, and the heat recovery efficiency up to 82%. It can prolong the heat pump units and the fresh air units run in the period of heating, guarantee well IAQ for a long time.
机译:本文分析了冬季寒冷和严重寒冷地区现有公共建筑空调系统空调系统的运行条件和现有问题,并比较了新鲜空气单元的防冻措施解决方案的分析,介绍了恢复排气能源热交换手段解决冬季空调系统现有问题。结果表明,室外温度从-25〜10°C变化,空气供应程度可达10度以上,这意味着恢复排气能量的系统可以预热新鲜空气超过10度。恢复COP新鲜空气热泵单元达到3.8以上,热回收率高达82%。它可以延长热泵装置和新鲜空气装置在加热期间运行,保证很长一段时间。