首页> 外文会议>International Conference on Advanced Design and Manufacturing Engineering >Theoretical gas phase compressibility factor of mixed refrigerants in auto-cascade refrigeration system
【24h】

Theoretical gas phase compressibility factor of mixed refrigerants in auto-cascade refrigeration system

机译:自动级联制冷系统混合制冷剂的理论气相压缩系数

获取原文

摘要

The compressibility factor is solved using the RKS equation and the corresponding calculation program. Redlich-kwong-Soave the numerical calculation method for solving the compressibility factor, R22 and CO_2 is calculated and compare it with standard values, so as to verify correctness of program. Finally, calculate the compressibility factor of mixed refrigerants R14/R23/R22 in a three-stage auto cascade system. At the same time, provide reference for solving it in auto-cascade system.
机译:使用RKS方程和相应的计算程序来解决压缩性因子。 Redlich-Kwong-Soove计算用于求解压缩因子,R22和CO_2的数值计算方法,并将其与标准值进行比较,以验证程序的正确性。最后,计算三级自动级联系统中混合制冷剂R14 / R23 / R22的可压缩因子。同时,为在自动级联系统中解决求解它的参考。