首页> 外文会议>IEEE PES International Conference and Exhibition on Innovative Smart Grid Technologies >A novel method for recovery of drainage power from distribution transformers
【24h】

A novel method for recovery of drainage power from distribution transformers

机译:一种从分配变压器恢复排水功率的新方法

获取原文

摘要

Non-linear loads have become a larger percentage of the total load in commercial facilities. The use of non-linear loads results in excessive injection of harmonic components from the customer facility onto the utility power system. Conventional distribution transformers are of delta-star type, providing 3-phase 4-wire ac distribution. In such a case, the triplen harmonic currents caused due to non-linear loads get circulated in the primary delta winding. But this leads to increased power losses, temperature rise and subsequent de-rating as well as reduction in life of transformers. This paper proposes a novel method for recovering the drainage power which is normally wasted in the delta winding of the distribution transformer. The experimental studies conducted on a three kVA transformer shows that when the drainage power of delta winding is recovered it helps in improving the transformer efficiency and system power factor.
机译:非线性载荷已成为商业设施总载荷的较大百分比。非线性载荷的使用导致从客户设施的过度注入来自顾客设施到公用电力系统。传统的分配变压器是Delta-Star类型,提供3相4线AC分布。在这种情况下,由于非线性负载引起的三平方谐波电流在初级Δ绕组中循环。但这导致功率损失增加,温度升高和随后的缩放以及变压器的寿命的减少。本文提出了一种用于回收排水功率的新方法,该方法通常浪费在分配变压器的达达绕组中。在三个kVA变压器上进行的实验研究表明,当恢复Delta绕组的排水功率时,它有助于提高变压器效率和系统功率因数。