Research on return voltage method to diagnose insulation moisture in transformer

机译:逆电压法诊断变压器绝缘水分的研究

获取原文

摘要

Moisture in power transformer strongly influences the dielectric properties of oil-paper insulation system. The insulation paper gradually degrades over time, therefore, it is imperative to assess integral condition of oil-paper insulation for assuring a normal operation of power transformers. As a non-destructive diagnostic technique, return voltage measurement is an effective assessment method of water content in transformer pressboard. The study presented in this paper aims of further investigating the reliability of the quantification of water content using dominant time constant in transformer pressboard. Field tests performed on several transformers in different status have shown that the return voltage measurement method can estimate the moisture content in paper insulation of power transformers effectively.
机译:电力变压器中的水分强烈影响油纸绝缘系统的介电性能。绝缘纸随着时间的推移逐渐降低,因此迫切需要评估油纸绝缘的整体条件,以确保电力变压器的正常运行。作为非破坏性诊断技术,返回电压测量是变压器压板中的水含量有效评估方法。本文提出的研究旨在进一步研究使用变压器压板中的主导时间恒定的水含量定量的可靠性。在不同状态下对多个变压器执行的现场测试表明,返回电压测量方法可以有效地估计电力变压器的纸质绝缘中的水分含量。