This paper describes the investigation of the insulation condition of a number of power and distribution type transformers of different manufacturing dates and with different operating histories. Return voltage measurements were conducted for these transformers. Effects of moisture and aging on the oilpaper insulation of these transformers were investigated and results are presented in this paper. Moisture in oil samples at known temperature was measured for these transformers. Previously accelerated aging experiments were performed on paper wrapped insulated conductors in different environments over a temperature range of 115 to 145 C. Results from the measurements on transformers are compared with those of the accelerated aged samples and are described in this paper.
机译:本文描述了对许多不同制造日期和不同运行历史的电力和配电型变压器的绝缘状况的研究。对这些变压器进行了返回电压测量。研究了水分和老化对这些变压器油纸绝缘的影响,并给出了结果。这些变压器在已知温度下测量了油样中的水分。先前的加速老化实验是在115至145 C的温度范围内的不同环境中对纸质包裹的绝缘导体进行的。将变压器的测量结果与加速老化样品的测量结果进行了比较,并在本文中进行了描述。