The weather conditions in Kuwait impose a difficult HVAC building operation due to the hot and arid climate. Most of the time, high ambient temperatures in Kuwait exceed 48°C, which result in difficult indoor comfort condition. Mosques are religious buildings with intermittent occupancy, due to their special cultural and religious requirements. In fact, prayers schedule is scattered throughout five daily times, with a maximum use around noon times on Fridays only. In addition, the number of mosques is increasing, due to population growth, and imposes high electrical load requirements on the public authorities in Kuwait. This paper demonstrates and analyzes thermal behavior of a typical mosque in the state of Kuwait. An energy audit is performed using state of the art building energy simulation software (Visual DOE 4.1). The simulation tool is intended to analyze the thermal behavior of the audited mosques and is used to asses potential energy conservation opportunities for future mosque design in Kuwait. Data collection including drawings, site visits and total daily kWh monitoring are performed to carry out the simulation analysis. It is found that an annual energy use savings up to 72% can be achieved through improvements of buildings envelope designs and operating strategies. In addition, life cycle cost LCC analysis is performed to make economical assessment of the energy conservation measures that are evaluated in this study. It was found that a LCC saving around 40% can be achieved with a simple payback period of less than 4 years.
机译:在科威特的天气条件下征收困难HVAC建筑施工,由于炎热和干旱气候。大部分时间,在科威特高环境温度超过48℃,其导致难以室内舒适条件。清真寺是间歇性占用宗教建筑,由于其特殊的文化和宗教的要求。事实上,祈祷时间表遍布每日时报5家,中午前后时间最大限度地利用上周五只。此外,清真寺的数量正在增加,由于人口增长,并规定在科威特公共机构的高电力负荷需求。本文演示和分析科威特状态的典型清真寺的热行为。能源审计是使用本领域建筑能耗分析软件(DOE可视4.1)的状态下进行的。仿真工具旨在分析被审计清真寺的热行为,并用于潜在驴节能机会在科威特未来清真寺的设计。进行数据收集,包括图纸,实地考察和每日总千瓦时监控进行仿真分析。研究发现,每年的能源使用节省高达72%能够通过建筑物的改进,可以实现信封的设计和操作策略。此外,执行生命周期成本LCC分析作出的,在这项研究进行评估节能措施的经济评估。结果发现,一个LCC节省40%左右可以用不到4年的简单投资回收期来实现。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号