首页> 外文会议>International Conference on Sustainable Power Generation and Supply >Simulation analysis of influence of MW-level grid-connected photovoltaic power station on distribution networks
【24h】

Simulation analysis of influence of MW-level grid-connected photovoltaic power station on distribution networks

机译:MW级网格连接光伏电站对配电网影响的仿真分析

获取原文

摘要

The modular simulation model of MW-level grid-connected photovoltaic (PV) power station is established at PSCAD/EMTDC. In this paper, simulation models according to different real engineering can be set up based on the modular flexible combinations. Next, power quality of PV power station and influence on distribution networks are studied. In addition taking a real system for example, the voltage deviation and the harmonic distortion (THD) of distribution networks connected with the different scale grid-connected photovoltaic power station are analyzed. The conclusion that voltage deviation of distribution networks may exceed limits of national standard with the expansion of PV capacity is drawn. This paper puts forward reactive power control method of the station based on synchronous PI current control. Finally, the harmonic current generated by the 10MW PV power station is analyzed.
机译:在PSCAD / EMTDC建立了MW级电网连接光伏(PV)电站的模块化仿真模型。在本文中,可以根据模块化灵活组合设置根据不同实际工程的仿真模型。接下来,研究了光伏电站的功率质量和分配网络的影响。另外,例如,分析了与不同刻度电网连接的光伏电站连接的分配网络的电压偏差和谐波失真(THD)。结论,分配网络的电压偏差可能超过国家标准的限制,绘制了PV容量的扩展。本文提出了基于同步PI电流控制的车站的反应功率控制方法。最后,分析了由10MW PV发电站产生的谐波电流。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号